Annex
BK2000 25
Part for byte-oriented
data, analog inputs
Relative byte
address
Bit position Process image in
the controller
Position in the
block
0, 1, 3, 4
none E0, E1, E2 POS10
5, 6, 7, 8
none E3, E4, E5 POS13
Part for non-byte-oriented
data, digital inputs
Relative byte
address
Bit position Process image in
the controller
Position in the
block
9
0 E6 POS01
9
1 E6 POS01
9
2 E6 POS02
9
3 E6 POS02
9
4 E6 POS03
9
5 E6 POS03
9
6 E6 POS04
9
7 E6 POS04
10
0 E7 POS05
10
1 E7 POS05
10
2 E7 POS06
10
3 E7 POS06
10
4 E7 POS15
10
5 E7 POS15
10
6 E7 POS16
10
7 E7 POS16
11
0 E8 POS17
11
1 E8 POS17
The positions POS14 and POS21 are not relevant in relation to the
exchange of data. They do not appear in the list. If a byte, e.g. E11, is not
used completely, the bus coupler pads the remaining bits of the byte with
zeros.
Overview of the breakdown of the process image in the bus coupler:
Output data in the
bus coupler
A0
...
byte-oriented data
...
A24
A25
bit-oriented data
A26
Input data in the
bus coupler
E0
...
byte-oriented data
...
E8
E9
...
bit-oriented data
...
E11
The base addresses E0 and A0 listed here are relative addresses or
addresses in the bus coupler. Depending on the higher-level field bus, the
addresses may be placed in a freely chosen position in the controller's
process image by the bus master. The master's configuration software