
PT100 4-fold temperature measurement Beckhoff II/O System
Page 10 of 10 Version : 1.1 Date : 12 March 97
5. Terminal diagram
Plug connection assignment and signal description
CONNECTOR X10
Plug Pin Signal
Description
X10 1 +
+24V supply voltage, control logic/analog
portion
X10 2 -
Ground
X10 3
Unassigned
CONNECTOR X10
Plug Pin Signal Description
X20 1 -
GND for PT100 sensor
X20 2 E1
Input, PT100 sensor pick-off
X20 3 E1
Input, PT100 sensor pick-off
X20 4 I1
Constant-current source for PT100 sensor
(1mA)
X20 5 -
GND for PT100 sensor
X20 6 E2
Input, PT100 sensor pick-off
X20 7 E2
Input, PT100 sensor pick-off
X20 8 I2
Constant-current source for PT100 sensor
(1mA)
X20 9 -
GND for PT100 sensor
X20 10 E3
Input, PT100 sensor pick-off
X20 11 E3
Input, PT100 sensor pick-off
X20 12 I3
Constant-current source for PT100 sensor
(1mA)
X20 13 -
GND for PT100 sensor
X20 14 E4
Input, PT100 sensor pick-off
X20 15 E4
Input, PT100 sensor pick-off
X20 16 I4
Constant-current source for PT100 sensor
(1mA)
Important: A bridge has to be inserted at the input for all of the unused channels. Open
inputs are capable of affecting the values of the other channels.
Example: If a PT100 sensor is not connected to channels 2 and 4, then pin 6 has to be
bridged with pin 7 and pin 14 with pin 15.
Comentários a estes Manuais