Product Description
Product Description
Appropriate Use
The DVI/USB extension can be used to operate CP68xx and CP78xx
series Control Panels up to a distance of 31 meters from the Industrial PC.
Do not use the modules in
potentially explosive
atmospheres
The modules must not be used in potentially explosive atmospheres.
Transmitter modules connections
Connections of the C9900-
A172 transmitter module
X 101
X 102
X 103
X 100
X 104
Pin assignment
Pin Signal Pin Signal
1
0 V
3
+ 24 V
2
GND
X 100
power supply
WAGO 734-103/ 037-000
Pin Signal Pin Signal
Housing
Screen
5
n.c.
1
TD +
6
RD -
2
TD -
7
n.c.
3
RD +
8
n.c.
X 101
USB Extension
RJ-45 connector (Ethernet 10/ 100 Mbit)
4
n.c.
- Signal Pin Signal
1
5V
3
D +
2
D-
4
GND
X 102
USB Upstream
USB PCB-installation B-Type
(FCI 61729-0010B USB Receptacle B-Type)