Beckhoff CX2100­00x4 Manual do Utilizador Página 19

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 45
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 18
Productoverview
ChangedsettingsarestoredfailsafeinBeckhoffdevices.
Ifthedeviceislaterexchanged,however,thesettingsthathavebeenchangedfromtheseriesstandardare
lost.TheEtherCATmastercanthenloadthechangedCoEparametersintothenewdeviceatstartup,ifitis
setupappropriately.
SothataCoEdirectoryisavailableofflineduringthepreparationforconfiguration,itcanbecontainedinthe
devicedescriptionasacopy.
TheextenttowhichtheCoEdirectoryissupporteddependsonthecapabilitiesoftheEtherCATmaster.
Tab:Online
thestatemachineoftheEtherCATcommunicationisdisplayedhere.Itcanalsobeswitchedtoadifferent
statehere.Thisisdonebyselectingthedesiredstatebyamouseclickontheappropriatebutton.The
individualstatesarebrieflydescribedbelow.Forfurtherinformation,pleaserefertotheEtherCATsystem
descriptiononourwebpage.
EtherCATStateMachine
ThestateoftheEtherCATslaveiscontrolledviatheEtherCATStateMachine(ESM).Dependinguponthe
state,differentfunctionsareaccessibleorexecutableintheEtherCATslave.Specificcommandsmustbe
sentbytheEtherCATmastertothedeviceineachstate,particularlyduringthebootupoftheslave.
Adistinctionismadebetweenthefollowingstates:
• Init
• PreOperational
• SafeOperationaland
• Operational
• Boot
TheregularstateofeachEtherCATslaveafterbootupistheOPstate.