Commissioning
Systembehaviorintheeventofasessionbeingendedbytheuser:Theassociatedsettingsdetermine
thesystembehavioriftheendofasessionwasnotinitiatedbytheUPSservice,butbytheuserorthe
application(theusermayhaveselectedshutdownorrestartviathestartbutton).
Endofsessionfrombattery:TheseoptionsdeterminethesystembehaviorifthePCwasrunningon
batteryatthetime(startoftheendofasession).
Endofsessionfrommainsvoltage:TheseoptionsdeterminethesystembehaviorifthePCwasrunning
onmainsvoltageatthetime(whentheendofasessionwasinitiated).
UPSoffandonagainifmainsvoltageOK:Ifthisoptionisselected,theUPS(andthePC)switchesoff
oncethedelaytimehaselapsedandimmediatelyonagainoncetheexternalpowersupplyisavailableagain
(powerONafterpowerfail).Thisisthedefaultbehaviorforallsystems,includingsystemswithSoft
PowerOffsupport.ThedelaytimeforswitchingofftheUPShastobeconfiguredviatheAlarm configuration
dialog [}52].IfthisoptionisselectedandthePCisbatteryoperated,thePCsmustnotberestarted!
OtherwisethePCmaybeswitchedoffduringthestartupphase!
DelayedUPSprotectionswitchoff(onlyforsystemswithoutSoftPowerOffsupport(StateS5)):If
thisoptionisselected,UPSprotectionisdeactivatedafteraconfigurabledelaytime,inordertoenablethe
PCandtheUPStobeswitchedoff(e.g.viathemainswitch).ThisoptionisonlysupportedbyBeckhoff
P24VxxxxUPSandUPSfirmwareversion>=33.1.I.Inothermodelsthisoptionisdeactivated.
DelaytimeforswitchingoffUPSprotection(s):Withshortertimes,thePC(andtheUPS)canbe
switchedoffmorequicklyafterashutdown.However,duringarestartthePCmaynotbefullyprotected
againstvoltagefailure.Withlongertimesandshutdown,ittakeslongerforthePC(andtheUPS)toswitch
off.Ontheotherhand,duringarestartthePCisprotectedduringthecompletestartupphase.Duringa
restart,UPSprotectionisactivatedbeforethedelaytimehaselapsed,oncetheUPSservicehasresumed
communicationwiththeUPS.Default:360seconds.
5.2.1.6 Aboutdialog
ThisdialogdisplaystheversioninformationfortheUPSsoftwarecomponents.
CX210009x4 57Version1.1