Beckhoff CX51x0 Manual do Utilizador Página 40

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 87
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 39
Mountingandwiring
4.10 RS422/RS485connections(CX51x0N031)
TheCX51x0N031systeminterfaceprovidesanRS422orRS485interface,COM1(X300).Itis
implementedona9poleSubDsocketstrip.Ifmorethanoneinterfaceisrequired,thesystemcanbe
extendedwiththerequirednumberofserialinterfacesusingtheterminalbus(KorEbus)andBus
Terminals(KL/EL6001).Thepinassignmentisshownatthebottomofthepage.
Themaximumbaudrateonbothchannelsis115kbit.Theinterfaceparametersaresetviatheoperating
systemorfromthePLCprogram.
COMinterface(socket)
PinassignmentoftheCOMinterface
PIN Signal Type Description
2 TxD+ DataOut+ Transmit422
3 RxD+ DataIn+ Receive422
5 GND Ground Ground
6 VCC VCC +5V
7 TxD DataOut Transmit422
8 RxD DataIn Receive422
ForRS485pins2and3(data+)mustbeconnected,andpins7and8(data–).
Settingtheinterfaceparameters
Theinterfaceisparameterizedasfollowsinthedeliverycondition:
RS485withoutecho,endpoint(terminated)standardsetting
Function Status
Echoon off
Echooff on
Autosendon on
Alwayssendon off
Autoreceiveon on
Alwaysreceiveon off
Termon on
Termon on
CX51x040 Version1.0
Vista de página 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 86 87

Comentários a estes Manuais

Sem comentários