Mountingandwiring
3.5 Powersupply
ThispowersupplyunitisequippedwithanI/Ointerface,whichpermitsconnectionoftheBeckhoffBus
Terminals.Thepowerissuppliedviatheupperspringloadedterminalslabelled“24V”and“0V”.
ThesupplyvoltagesuppliestheCXsystemanttheterminalBusandBusTerminalwithavoltageof24VDC
(15%/+20%).Thedielectricstrengthofthepowersupplyunitis500V
rms
.SincetheTerminalBus(Kand
Ebus)onlytransfersdata,aseparatepowersupplyisrequiredfortheBusTerminals.Thisisprovidedby
meansofthepowercontacts,whicharenotconnectedtothepowersupply.
Requirementsforthe24Vpowersupply
InordertoguaranteetheoperationoftheCPU(CX20x0module)andtheterminalstrandinallcases,the
powersupplymustsupply4Aat24V.
Theterminalsareimplementedinspringforcetechnology.Connectthecablesasfollows:
1. Openaspringloadedterminalbyslightlypushingwithascrewdriverorarodintothesquareopening
abovetheterminal.
2. Thewirecannowbeinsertedintotheroundterminalopeningwithoutanyforce.
3. Theterminalclosesautomaticallywhenthepressureisreleased,holdingthewiresecurelyand
permanently.
CX2020,CX2030,CX2040 25Version1.2