Mountingandwiring
3.11 RS422/RS485connections(CX20x0N031)
TheCX20x0N030systeminterfaceprovidesanRS422orRS485interface,COM1(X300).Itis
implementedona9poleSubDsocketstrip.Ifmorethanoneinterfaceisrequiredthesystemcanbe
extendedviatheTerminalBus(KorEbus)orBusTerminals(KL/EL6021)whichprovideserialinterfaces.
Thepinassignmentisshownatthebottomofthepage.
Themaximumbaudrateonbothchannelsis115kbit.Theinterfaceparametersaresetviatheoperating
systemorfromthePLCprogram.
COMinterface(socket)
Table7:PinassignmentoftheCOMinterface
PIN Signal Type Description
2 TxD+ DataOut+ Transmit422
3 RxD+ DataIn+ Receive422
5 GND Ground Ground
6 VCC VCC +5V
7 TxD DataOut Transmit422
8 RxD DataIn Receive422
ForRS485pins2and3(data+)mustbeconnected,andpins7and8(data).
Settingtheinterfaceparameters
Theinterfaceisparameterisedasfollowsinthedeliverycondition
Table8:RS485withoutecho,endpoint(terminated)standardsetting
Function Status
Echoon off
Echooff on
Autosendon on
Alwayssendon off
Autoreceiveon on
Alwaysreceiveon off
Termon on
Termon on
CX2020,CX2030,CX2040 33Version1.2