Errorhandlinganddiagnostics
LEDsforKbusdiagnostics
Errorcode Errorcodeargu
ment
Description Remedy
Persistent,
continuous
flashing
EMCproblems Checkpowersupplyforundervoltageor
overvoltagepeaks
ImplementEMCmeasures
IfaKBuserrorispresent,itcanbe
localizedbyarestartofthepowersupply
(byswitchingitoffandthenonagain)
1pulse 0 EEPROMchecksum
error
Reverttothemanufacturer’ssetting
1 Codebufferoverflow InsertfewerBusTerminals.Toomanyentriesin
thetablefortheprogrammedconfiguration
2 Unknowndatatype Softwareupdaterequiredforthepowersupply
2pulses 0 Programmed
configurationhasan
incorrecttableentry
Checkprogrammedconfigurationfor
correctness
n(n>0) Tablecomparison
(BusTerminaln)
Incorrecttableentry
3pulses 0 Kbuscommanderror NoBusTerminalinserted
OneoftheBusTerminalsisdefective;
halvethenumberofBusTerminals
attachedandcheckwhethertheerroris
stillpresentwiththeremainingBus
Terminals.RepeatuntilthedefectiveBus
Terminalislocated.
4pulses 0 KBusdataerror,
breakbehindthe
powersupply
Checkwhetherthen+1BusTerminaliscorrectly
connected;replaceifnecessary.
n BreakbehindBus
Terminaln
CheckwhethertheBusEndTerminal9010is
connected.
5pulses n Kbuserrorinregister
communicationwith
BusTerminaln
Exchangethen
th
busterminal
7pulses 0 Processdatalengths
ofthesetandactual
configurationsdonot
correspond
Checkconfigurationandterminalsfor
consistency
9pulses 0 Checksumerrorin
Flashprogram
Reverttothemanufacturer’ssetting
n(n>0) BusTerminalnisnot
consistentwiththe
configurationthat
existedwhentheboot
projectwascreated
Reverttothemanufacturer'ssettingwhichwill
clearthebootproject.
14pulses n n
th
BusTerminalhas
thewrongformat
Startthepowersupplyagain,andiftheerror
occursagainthenexchangetheBusTerminal.
15pulses n NumberofBus
Terminalsisnolonger
correct
Startthepowersupplyupagain.
16pulses n LengthoftheKBus
dataisnolonger
correct
Startthepowersupplyupagain.